Thread type: E - Electrical cable glands thread DIN EN 50 262

 

The table for the E thread contains all relevant information for threads for electrical cable glands according to DIN EN 50 262. The E thread according to the table is a relatively new standard that replaces the older armored conduit thread Pg with a newer standard. The old, imperial system has been replaced by uniform metric dimensions, as you can see in the E thread table. The main reason for the change was that the old Pg system was mainly used in Germany. The new standard according to the E thread table adapts the dimensions for cable glands to the international metric standard. The E thread has a flank angle of 60°. According to the E thread table, cable glands are primarily found on electrical installation conduits, cable glands and cable entries, junction boxes, distribution boxes, junction boxes and terminal boxes. Before starting work, always make sure that you are actually working with the correct standard according to the E thread table, as E and Pg threads are not interchangeable.

The table for the E thread for cable glands is made up of two parts. The first E thread table shows the dimensions of the mounting holes for cable glands. In the first line you will see a numerical value that indicates the nominal diameter. This is followed by the thread size, expressed by the abbreviation M for the metric standard thread and again the nominal diameter as a numerical value. In the next line you will see the thread designation according to the table E Thread. The abbreviation here is E, the numerical value corresponds to the thread size. Finally, the first table for the E thread contains information on the corresponding diameter of the mounting hole. The second table for the E thread again contains information on the nominal diameter, thread size and thread designation. These correspond to the values from the first E thread table. However, instead of the mounting hole, the second E thread table now refers to the diameter of the core hole for the threaded hole. In order to carry out a correct installation, you must adhere exactly to the values from both tables for the E thread.

The EN 50 262 was adopted on 01.04.1998 and published in Germany in April 1999, DIN EN 50262 / VDE 0619. The well-known standards for cable glands, such as DIN VDE 0619 (VDE 0619) :1987-09, DIN 46319: 1989-12, DIN 46320-2 and DIN 46320-1:1985-09 .... -4: 1973-01 etc ., were still allowed to be applied to 31.12.1999.
In this standards issued sign permits were valid until 01.03.2001. For another 2 years, ie up to 28.02.2003, there is a sales permit for the inventory of ready-made end products.

  1. Scope of EN 50 262: This European Standard contains requirements and tests for the design and construction of cable glands. This standard covers complete cable glands from ...... but not parts of cable glands.
  2. The thread of cable glands must be constructed in accordance with Table 1 of EN 60423. This thread sizes are: M6x0,75; M8x1; M10x1; M12x1,5; M16x1,5; M20x1,5; M25x1,5; M32x1,5; M40x1,5; M50x1,5; M63x1,5 und M75x1,5.
  3. Mounting holes must have the ​​given values from Table 1; thread core holes acc. to table 2

Table 1: Mounting holes for cable glands

 6810121620253240506375
Thread SizeM 6M 8M 10M 12M 16M 20M 25M 32M 40M 50M 63M 75
Thread designationE 6E 8E 10E 12E 16E 20E 25E 32E 40E 50E 63E 75
diameter of
mounting hole
6,58,510,512,516,520,525,532,540,550,553,575,5

Table 2: Core hole for cable glands

 6810121620253240506375
Thread SizeM 6M 8M 10M 12M 16M 20M 25M 32M 40M 50M 63M 75
Thread designationE 6E 8E 10E 12E 16E 20E 25E 32E 40E 50E 63E 75
diameter of
core hole
5,257910,514,518,523,530,538,548,561,573,5

All data, tables, and values ​​are taken from the DIN EN 50 262 This standard also include further testing (electrical properties, IP code, etc.), which are required for classification and identification of cable glands.

Comparison cable glands PG-thread (old standard) - EL (new standard):

Cross section of an E thread